Detailed

 

Model GSS50360 GSS60360 GSS80360 GSS100360 GSS120360 GSS160360
CAPACITY 50KVA/40Kw 60KVA/48KW 80KVA/64KW 100KVA/80KW 120KVA/96KW 160KVA/120KW
Rated voltage 3×38ovAc/40ovAC(3-phase +N line)
Voltage Range 285VAC~475VAC
Frequency Range 50/60 Hz土10 %
Output Voltage 3×380VAC/400VAC(3-phase+N        line)
Voltage stability steady state:土1%
transient:±5%(load change 100-0-100%)
Frequency
synchronization range
Mains lost±0.1 Hz
Mains lost±0.1 Hz
tracking rate ±1 Hz/s
WaveForm pure sine wave
total harmonics(THDv) <2%(Linear load)<5%(nonlinear load)
Phase unbalance 120° 1%(balance load)120°土2%(50%un-balance load)
Dynamically
adjust time
<60ms  90%return to 90%of rated value
overload capacity 110%~150%for 10min-1min;150%~>160%for 1min~200ms;>160%for 200ms
crest factor 3:1
Load power factor range 0.6~1(capacitive or inductive)
Unbalanced output voltage
@100%unbalanced load
<1%
protect or restrict Extremely heavy overload;short circuit,voltage ms limit inrush
                                      current peak voltage limit
Overall efficiency  
AC MODE 91% 92%
AC MODE 92% 93%
BY PASS TYPE static switch
BY PASS VOLTAGE 3×380VAC/400VAC
FREQUENCY 50/60 Hz
CONTROLLER microprocessor
Inverter
to Bypass Transfer Time
sync mode:Oms,Asynchronous mode:10ms
overload capacity 150%~180%1h~30s;180%~>200%30s~200ms;200ms for>200%
switch to bypass Overload 160%:switch immediately
switch back
to contravariance
Automatically switch after alarm is cleared
Maintenance bypass  
Type Uninterrupted
VOLTAGE 3×400v(3 phase +N line)
FREQUENCY 50/60 Hz
Charging &batteries  
Number of batteries(12v) 29/30/31/32(Adjust)
charging method Optional:constant voltage charging/constant current charging
recharging current ADefault 10A,Max 40A
Battery Type Gel battery,Sealed lead-acid battery,nickel-chromium battery,lithium battery